Settings/setup example
The following drawing shows the relation between the value of the AO signal selected
and its corresponding values at the terminal pin. For settings see table below the
drawing.
Example: which maps the values 0 - 1000
of the analog manager onto the hardware
level 4 – 20 mA
Maximum hardware
level = 20
Miniumum hardware
level = 4
y: Hardware level (output level
eg: [mA])
4
0
10
1000
0
Sour
ce value
at
maximum level
= 1000
Sour
ce value
at
minimum level
= 0
x: Source value (result of the
analogmanager)
20
Fig. 157:
Example to setup AO for 0 to 1000 IN becomes OUT 4 to 20 mA
Parameter / AnalogManager
Example 3 with AO 1
ID
Selected hardware type
(For details refer to
)
5201
mA
Minimum hardware level
5208
4
Maximum hardware level
5209
20 mA
PWM output level
(visible only if »PWM« selected)
5210
—
Source value at minimum level
5204
0
Source value at maximum level
5206
1000
Filter time constant
5203
3
AM Data source AO1
5200
Type: Pass through
A1 = analog variable with range
0 to 1000
Analog output 1
10310
Display of resulting value
252
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.5.1 Analog Outputs 1 and 2