• "04.01 Operat. mode AUTO" and
•
• "01.08 Warning alarm" is active.
•
Configuring "Relay 2" for a pulsing relay
⚙
1. ▷
Fig. 225:
LogicsManager function "Relay 2"
Configure the LogicsManager function "Relay 2" as shown in (
).
▶
In this example is the Delay ON time (2 s) in the LogicsManager determines how long
the pause is, the Delay OFF time (0.5 s) the pulse duration.
6.3.4
Changing A Starter Battery Set
This function is set up with the LogicsManager.
The following programming example shows how two relay outputs are energized in turns
when discrete input 9 is energized.
At first discrete output 11 will be energized, then, discrete output 12 will be energized,
then discrete output 11 and so on.
This logic may be used to change between two starter battery sets for each starting
cycle.
Configuration
Configure Relay 11 and Relay 12 as well as the Flags 2, 3, 4, and 5 as shown in the
following example.
You may also use the discrete input, which starts the engine by default [DI 02] or any
other input command instead of discrete input 9; for example the command variable
"03.06 Engine released".
⚙