ID
Parameter
Setting range
[Default]
Description
defines when 95% of the original
setpoint jump is reached.
Note: Input 0.0s disables the filter
influence.
Interface reference setpoint VQ0
AnalogManager variable “05.46 VQ0 reference”
No.
Description
Value
Meaning
512
Control 10
INT16
Interface reference
value VQ0. Resolution
(1/100)
VQ0: The “starting”
value is 1.00.
The value is limited
according to the
configuration setting.
Analog source: Interface reference setpoint VQ0
This can be picked up with the AnalogManager variable “05.46 VQ0 reference”
Visualization Q(V) reactive power characteristic
Actual value V/Vc ID10353
Q/Pinst reference ID 10347
QV reference [kvar] ID 10359
Configuration Test possibility for reactive power Q(V) characteristic
For test purposes it is possible to configure a "Test mains voltage" which is passed to the
Q(V) characteristic instead of the real mains voltage measurement.
ID
Parameter
Setting range
[Default]
Description
5828
Enable mains test voltage
On
[Off]
For test purposes, use the mains
test voltage instead of the
measured mains voltage. This
function is temporarily enabled.
On: The mains test voltage is
used for Q(V) reactive power
characteristic. This function is
reset after 1 hour automatically.
Off: The test voltage is disabled
and the measured mains voltage
is used.
Note: Only in toolkit!
321
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.5.1 Reactive power Q(V)