9.5.5.10 CAN J1939 (ECU) Monitoring
Message text
ID
Meaning
J1939 dev. 1 timeout
10059
J1939 device 1 timeout
Messages from the J1939 device 1 are missing. (CAN2)
J1939 dev. 2 timeout
10091
J1939 device 2 timeout
Messages from the J1939 device 2 are missing. (CAN2)
J1939 dev. 3 timeout
10092
J1939 device 3 timeout
Messages from the J1939 device 3 are missing. (CAN2)
J1939 ECU timeout
10058
J1939 ECU timeout
Messages from the J1939 ECU are missing. (CAN2)
Red stop lamp
15125
Red stop lamp, J1939 interface
The ECU sends a red stop lamp signal. There is a critical failure detected in the
ECU.
Amber warning lamp
15126
Amber warning lamp, J1939 interface
The ECU sends a amber warning lamp signal. There is a warning failure detected in
the ECU.
J1939 Emission lamp
10663
J1939 Emission lamp
ECU has an Emission/Malfunction alarm.
J1939 Protect lamp
10662
J1939 Protect lamp
ECU has a protect alarm.
9.5.5.11 Ethernet Communication Monitoring
Message text
ID
Meaning
Ethernet issue
11852
Abnormal rate of Ethernet messages.
The device detects an abnormal high rate of Ethernet UDP-messages per time
scale.
9.5.5.12 Multi-unit Monitoring
Message text
ID
Meaning
Parameter alignment
4073
LDSS parameter mismatch detected
The easYgen has detected that not all LDSS parameters are configured identically
at all participating units.
Refer in the manual to the chapter "Multi-unit Parameter Alignment" to see the
relevant LDSS parameter.
Missing easYgen
4059
Missing easYgen
1188
easYgen-3000XT Series
B37574
9 Appendix
9.5.5.10 CAN J1939 (ECU) Monitoring
Released