ID
Parameter
CL
Setting range
[Default]
Description
Notes
For details please refer to
the manual of your J1939
ECU manufacturer.
This parameter is only
visible if "Device type"
(parameter
configured to "ADEC ECU8
MTU" and "ECU remote
controlled" (parameter
) is configured to
"On".
15164
ECU seq. B_IN_1
2
Determined by
LogicsManager 86.31
[(0 & 1) & 1]
= 11647
This LogicsManager is
prepared to pass binary
information to the ECU.
Right now it is only used
for:
ADEC ECU 9 "Rapid
Engine Start" (SPN 3542)
If the easYgen is
transmitting a start
command and the result of
“86.31 LM: ECU seq.
B_IN_1”is:
False, the ECU9 will start
with "Normal Engine Start"
True, the ECU9 will start
with "Rapid Engine Start"
EMS2 Volvo “Override”
(Engine restored operation)
If the result of "86.31 LM:
ECU seq. B_IN_1" is:
False: The Volvo override
flag is only active if LM
“04.27 Critical mode”
True: The Volvo override
flag is active independent
of LM “04.27 Critical mode”
S8 Scania “Desorption
Granted Status” (of ADC
Aftertreatment Desorption
Control)
637
easYgen-3000XT Series
B37574
4 Configuration
4.7.4.2.2 J1939 Interface
Released