Parameter Uprating
ID
Parameter
Setting range
[Default]
Description
5093
Function
On
[Off]
The f depending uprating of power can
be enabled here.
On: Active power uprating is enabled.
Off: Active power uprating is disabled
5094
f start value
15.00 to 85.00 Hz
[49.80 Hz]
If the mains frequency is lower than the
start value the frequency depending
uprating function is enabled.
5095
f stop value
15.00 to 85.00 Hz
[49.85 Hz]
The frequency depending uprating
function stops, if the mains frequency is
higher than the stop value.
5096
f dep.uprating
1 to 100 %/Hz
[40 %/Hz]
Depending on the actual mains
frequency, the generator active power
increases with the gradient value in
relation to the active power the
reference value.
Configuration Test possibility for f dependent up/derating
For test purposes it is possible to configure a "Mains voltage test frequency" which is
passed to the uprating and derating characteristics.
ID
Parameter
Setting range
[Default]
Description
5808
Enable mains test frequency
On
[Off]
For test purposes it is possible to
configure a "Mains voltage test
frequency" which is passed to the
uprating and derating
characteristics.
On:The mains test frequency is
used for f- dependent up-/derating
instead of the measured mains
frequency.
Off: The test frequency is disabled
and the measured mains
frequency is used.
Note:Enable mains test
frequency" is reset to Off
automatically after 1 hour.