4.4.3.1.2
Synchronization GCB/MCB
The following applies to application modes
A03
and
A04
.
The synchronization is active, if the following conditions are met simultaneously.
The display indicates "Synchronization GCB" or "Synchronization MCB".
Automatic operation
• The operating mode AUTOMATIC has been selected
•
• The mains voltage is available and within the configured operating range (
•
“4.5.3.3 Mains Operating Ranges”
• The generator and busbar voltage are available and within the configured operating
•
range (
╚═▷ “4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”
• The differential frequency/voltage is within the configured operating range
•
• Synchronizing the MCB
•
◦ The GCB is closed (or at least one GCB is closed in a multiple genset
◦
application)
◦ The busbar voltage is within the configured operating range
◦
) signal is present, for example
◦
discrete input 6 is energized if configured as DI 6
• Synchronizing the GCB
•
◦ The MCB is closed
◦
◦ The busbar voltage is within the configured operating range
◦
◦ Engine delayed monitoring (parameter
◦
(parameter
) have expired or "Undelay close GCB" (parameter
Manual operation
• Operating mode MANUAL has been selected
•
• The generator and busbar voltage are available and within the configured operating
•
range (
╚═▷ “4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”
• The differential frequency/voltage is within the configured operating range
•
• Synchronizing the MCB
•
◦ The GCB is closed (or at least one GCB is closed in a multiple genset
◦
application)
◦ The busbar voltage is within the configured operating range
◦
) signal is present, for example
◦
discrete input 6 is energized if configured as DI 6
266
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.1.2 Synchronization GCB/MCB
Released