ID
Parameter
CL
Setting range
[Default]
Description
5631
Reactive power load
share
2
[On]
Reactive power load share is
enabled. When multiple
generators are operating in
parallel, the reactive power is
shared proportionally.
Off
Reactive power load share is
disabled
4543
React. power load
share gain
2
0.01 to 9.99
[1.25]
This parameter defines the impact
of the reactive power load sharing
error signal on the voltage/
reactive load controller setpoint.
The reactive power load share
gain can be adjusted between
0.01 to 9.99.
The reactive load controller
setpoint is considered, if an
export/import reactive power
control to mains is maintained.
With a higher value the reactive
load sharing has a higher
correction factor in the regulation.
Notes
This parameter replaces the
former existing weighting factor of
non-XT easYgen (ID 5630). The
default gain 1.25 relates to the
50% value.
High data volume on communication ports can cause low HMI display operation dynamic.
Recommendation:
Reduce data transfer volume on CAN bus. This can be done with parameter
»Transfer rate LS fast message«.
A general action to reduce data volume on CAN1 is disabling the TPDO1 data protocol if it
is not used. Therefore navigate to parameter
»COB-ID« and enter "80000000"
via front panel or "2147483648" via ToolKit.
For more information how to reduce bus load see
.
Relation "... factor" <> "... gain"
This ... gain parameter replaces the former existing (%) ... factor of non-XT easYgen. The
table below shows the relation between the old and new values.
The used defaults 1.25 / 50% ensure backward compatibility.
Weighting %
LS Gain
10
2.25
20
2
334
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.3.7 Parameters