Bit number
Value
Meaning
1
PDO does not exist / is not valid
30
X
N/A
29
X
N/A
28-11
0
Always 0
10-0 (LSB)
X
Bits 10-0 of COB-ID
PDO valid / not valid allows to select, which PDOs are used in the operational state.
Transmission types
Parameters
are used to select one of
the following transmission types.
Transmission
type
PDO transmission
Cyclic
Acyclic
Synchronous
Asynchronous
RTR only
0
Will not be sent
1-240
X
X
241-251
Will not be sent
252
Will not be sent
253
Will not be sent
254
X
255
X
A value between 1 and 240 means that the PDO is transferred synchronously and
cyclically. The transmission type indicating the number of SYNC messages, which are
necessary to trigger PDO transmissions.
Transmit PDOs are always triggered by the following SYNC upon reception of data
independent of the transmission types 0 to 240. For TPDOs, transmission type 254 and
255 means, the application event is the event timer.
ID
Parameter
CL
Setting range
[Default]
Description
9600
9610
9620
9630
COB-ID
2
1 to FFFFFFFF hex
[80000000 hex]
This parameter contains the
communication parameters for
the PDOs the unit is able to
transmit. The unit transmits data
(i.e. visualization data) on the CAN
ID configured here.
615
easYgen-3000XT Series
B37574
4 Configuration
4.7.4.1.3 Transmit PDO {x} (Process Data Object)