DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
DI 9
DI 10
DI 11
DI 12
MCB
open
only
GCB
open
only
Delay
1200
1220
1240
1260
1280
1300
1320
1360
1380
1205
1225
Oper‐
ation
1201
1221
1241
1261
1281
1301
1321
1361
1381
1206
1226
Alarm
class
1202
1222
1242
1262
1282
1302
1322
1362
1382
1207
1227
Self
ack‐
now‐
ledg‐
ed
1204
1224
1244
1264
1284
1304
1324
1364
1384
1209
1229
Enabled 1203
1223
1243
1263
1283
1303
1323
1363
1383
1208
1228
Table 45: Discrete inputs - parameter IDs
ID
Parameter
CL
Setting range
[Default]
Description
1400
Description
2
user defined (up to 39 characters)
for default see
If the discrete input is enabled
with alarm class, this text is
displayed on the control unit
screen.
The event history will store this
text message as well.
Notes
This parameter may only be
configured using ToolKit. 19
characters are best for HMI
readability - text strings with 20
and more characters but without a
blank in between are NOT visible
as headline on DI {x} detail
screen. DI selection screen on
HMI/display works fine with up to
30 characters; others are
overwritten by mandatory screen
symbols. Please verify the length
on the display for best view.
If the DI is used as control input
with the alarm class "Control", you
may enter here its function (e.g.
external acknowledgment) for a
better overview within the
configuration.
1200
Delay
2
0.08 to 650.00 s
[0.20 s]
A delay time in seconds can be
assigned to each alarm or control
input.
The discrete input must be
enabled without interruption for
the delay time before the unit
reacts.
236
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.2 Discrete Inputs
Released