ID
Parameter
CL
Setting range
[Default]
Description
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
8833
Enabled
4
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
8808
Mains decoupling
volt.incr.
2
On
Voltage increase monitoring does
cause a decoupling.
[Off]
Voltage increase monitoring does
not cause a decoupling.
8850
Volt.incr.average
0
—
This visualization value shows the
current 10 minute average
voltage.
Notes
If 8849 is configured to AND, this
value is the minimum value
otherwise the maximum value of
the averages.
If "Mains voltage monitoring"
(parameter
configured to ALL, this value is
derived from the ”Phase -
Phase“ values.
4.5.3.10 Mains Time-Dependent Voltage
General notes
Two Time Dependent Mains Voltage Monitors Available
Both monitors behave similar but each with a separate Fault-Ride-Through (FRT) curve.
509
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.10 Mains Time-Dependent Voltage
Released