ID
Parameter
CL
Setting range
[Default]
Description
During an emergency start this
delay time "auxiliary prerun" is
not initialized. The engine will be
started immediately.
3301
Auxiliary services
postrun
(Coasting auxiliary
operation (post
operation))
2
0 to 9999 s
[0 s]
After each engine stop (the engine
stop timer has expired), the
discrete output for the auxiliary
services postrun (LogicsManager
03.31) remains energized for an
adjustable time (i.e. operate a
cooling pump).
If the operating mode is changed
from MANUAL to STOP or
AUTOMATIC without a start
command the relay remains
energized for this period of time.
The message "Aux.serv.postrun"
will be displayed on the control
unit screen. In the "MANUAL"
operating mode this relay output
is not used.
4871
Inhibit cranking
2
Determined by LogicsManager
87.66
[(0 & 1) & 1]
= 11455
Once the conditions of the
LogicsManager have been fulfilled
the cranking (03.38) is blocked.
The discrete output relay [R 03]
will be not energized.
Notes
For information on the
LogicsManager and its default
settings see
.
Please refer to
details.
12951
Firing speed
detection
2
Determined by LogicsManager
87.68
[(02.34 Firing speed electr. OR
02.35 Firing speed rpm) & 1]
= 11457
This LogicsManager allows
different sources to generate the
general firing speed flag. This will
be taken into account for the
START/STOP automatic and some
monitoring functions.
Notes
The former easYgen was fixed to
the electrical frequency always
and allowed other sources
additionally. The default setting
here is backward compatible.
12989
Speed detection
2
Determined by LogicsManager
87.69
[(02.36 Speed electr. OR 02.37
Speed rpm) & 1]
= 11458
This LogicsManager allows
different sources to generate the
general speed flag. This will be
taken into account for some
monitoring functions.
Notes
The former easYgen was fixed to
the electrical frequency always.
The default setting here is
backward compatible.