3.3
Setup Connections
NOTICE!
Avoid electrostatic discharge!
Before working with terminals please read and follow the instructions of chapter
For CAN and RS485 shielded cabling, no more than 25 mm wiring exposed without shield
coverage are allowed at terminal plug side.
General notes
NOTICE!
Malfunctions due to literal use of example values
All technical data and ratings indicated in this chapter are merely listed as examples.
Literal use of these values does not take into account all actual specifications of the
control unit as delivered.
• For definite values please refer to chapter
•
Wire sizes
Field wiring shall be made with use of cables which have temperature rating not less
than 90 °C.
AWG
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
mm²
30
0.05
21
0.38
14
2.5
4
25
3/0
95
600MCM
300
28
0.08
20
0.5
12
4
2
35
4/0
120
750MCM
400
26
0.14
18
0.75
10
6
1
50
300MCM
150
1000MCM
500
24
0.25
17
1.0
8
10
1/0
55
350MCM
185
22
0.34
16
1.5
6
16
2/0
70
500MCM
240
Table 1: Conversion chart - wire sizes