ID
Parameter
CL
Setting range
[Default]
Description
kvar. Note: Even the value is also
configurable as negative value do
not enter a negative value in this
mode.
Mains PF: The value entered as
PF/kvar setpoint is a mains power
factor setpoint at the interchange
point to mains.
Gen.kvar: The value entered as
PF/kvar setpoint is a generator
kvar power setpoint (-99999.9 to
99999.0 kvar). Note: A negative
value is accepted as a capacitive
kvar setpoint. A positive value is
accepted as inductive setpoint in
this mode.
5620
Int. power factor
setpoint 1
2
-0.999 to +1.000
[+1.000]
The desired power factor may be
configured here so that the
reactive power is regulated in the
system.
The designations "+" and "-"
stand for inductive/lagging
(generator overexcited) and
capacitive/leading (generator
underexcited) reactive power.
This setpoint is active only in
mains parallel operation.
5744
PF/kvar setpoint 2
mode
[Gen.PF]
Mns.Export kvar
Mns.Import kvar
Mains PF
Gen.kvar
Determination of the reactive
power control argument (Modes)
Gen.PF: The value entered as PF/
kvar setpoint is a generator power
factor setpoint.
Mns.Export kvar: The value
entered as PF/kvar setpoint is a
mains export power setpoint in
kvar. Note: Even the value is also
configurable as negative value do
not enter a negative value in this
mode.
Mns.Import kvar: The value
entered as PF/kvar setpoint is a
mains import power setpoint in
kvar. Note: Even the value is also
configurable as negative value do
not enter a negative value in this
mode.
Mains PF: The value entered as
PF/kvar setpoint is a mains power
factor setpoint at the interchange
point to mains.
Gen.kvar: The value entered as
PF/kvar setpoint is a generator
kvar power setpoint (-99999.9 to
99999.0 kvar). Note: A negative
value is accepted as a capacitive
kvar setpoint. A positive value is
accepted as inductive setpoint in
this mode.
309
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.2 Configure Power Factor / kvar Control
Released