ID
Parameter
Setting range
[Default]
Description
6912
V/Vc point 1
0.94
Configuration points (reference
points 1 to 4) with voltage level in
relation to the supply voltage (Vc)
and the reactive power in relation
to the installed active power from
the power generation device. The
installed active power is normally
the rated power.
V:
Range 0.00 to 1.50
Format 0.00
Q:
Range -0.5 to 0.50
Format 00.00
6913
Q/Pinst. point 1
-0.33
6914
V/Vc point 2
0.96
6915
Q/Pinst. point 2
0
6916
V/Vc point 3
1.04
6917
Q/Pinst. point 3
0
6918
V/Vc point 4
1.06
6919
Q/Pinst. point 4
0.33
1899
Q(V) limit setpoint filter
0 to 99.9 s
[10.0 s]
The PT1-filter for the reactive
power characteristic Q(V) limit can
be configured here. The
parameter stands for the 3 times
tau value of a PT1 element. (see
drawing). That means the
configured time defines when 95%
of the original setpoint jump is
reached.
Note: Input 0.0s disables the filter
influence.
6908
AM Q/P reference offset
AnalogManager
10.02 ONE
10.01 ZERO
0.0
02.01 LM FALSE
02.01 LM FALSE
Pass through
This value defines the offset for
the reference points 2 and 3.
AM Q/P reference offset
81.32
Analog result of AnalogManager
LM Q/P reference offset
81.32
Binary result of AnalogManager
Interface reference setpoint Q/P limit offset
AnalogManager variable "05.47 Interface QP offset"
No.
Description
Value
Meaning
513
Control 10
INTEGER16
Interface reference
value Q/P offset.
Resolution (1/100)
Q/P offset: The
“starting” value is 0.
The value is limited
according to the
configuration setting.
327
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.5.3 Reactive Power Q(V) limit
Released