ID
Parameter
CL
Setting range
[Default]
Description
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
Monitoring Parameter Alignment VDE AR-–4105
The following parameters are compared for monitoring its alignment:
Control
Parameter ID
Parameter
Mains Decoupling
3110
Mains Decoupling
Overfrequency level 2
2856
Monitoring
2860
Limit
2861
Delay
Underfrequency level 2
2906
Monitoring
2910
Limit
2911
Delay
Overvoltage level 2
2956
Monitoring
2960
Limit
2961
Delay
Undervoltage level 2
3006
Monitoring
3010
Limit
3011
Delay
Mains voltage increase
8806
Monitoring
8808
Mains decoupling volt.incr.
8807
Limit
Change of frequency
3058
Change of frequency
3054
Phase shift: Limit 1-phase
3055
Phase shift: Limit 3-phase
3104
Limit (df/dt)
3105
Delay (df/dt)
Disable mains monitoring
15159
Set TRUE
Table 66: VDE 4105 alignment: Supervised parameters
ID
Parameter
CL
Setting range
[Default]
Description
5131
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class C]
The alarm class specifies what
action should be taken if the
parameter alignment between the
communication devices(s) of the
AR-–4105 system is active.
497
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.4.1 Setup Grid Code AR-–4105
Released