ID
Parameter
CL
Setting range
[Default]
Description
This parameter is only visible if
power factor control (parameter
) is configured to "3pos
controller".
5662
Gain factor
1
0.1 to 10.0
[5.0]
The gain factor K
p
influences the
operating time of the relays.
By increasing the number
configured in this parameter, the
operating time of the relay will be
in-creased in response to a
deviation from the power factor
reference.
By increasing the gain, the
response is increased to permit
larger corrections to the variable
to be controlled.
The farther out of tolerance the
process is the larger the response
action is to return the process to
the tolerance band. If the gain is
configured too high, the result is
excessive overshoot/undershoot
of the desired value.
Notes
This parameter is only visible if
power factor control
(parameter
configured to "3pos controller".
5667
Cycle time factor
1
1.0 to 20.0
[1.0]
The cycle time factor adjusts the
time between the pulses (pause
time).
By increasing the cycle time
factor, the time between the
pulses increases.
Notes
This parameter is only visible if
voltage control (parameter
) is configured to "3pos
controller".
5663
Expand deadband
factor
1
1.0 to 9.9
[1.0]
If the measured generator power
factor is within the deadband
range (parameter
) and
the configured delay expand
deadband time (parameter
) expires, the deadband will
be multiplied with the factor
configured here.
Notes
This parameter is only visible if
power factor control
(parameter
configured to "3pos controller".
5664
Delay expand
deadband
1
1.0 to 9.9 s
The measured generator power
factor must be within the
deadband range for the time
307
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.2 Configure Power Factor / kvar Control