Modbus-
Address
Size
Index
Description
Unit
Scale
Model
ECU red lamp alarm
Mask: 0002h
All
ECU yellow (amber) lamp alarm
Mask: 0001h
All
50117
uint16
10190
BITLIST Alarms 3 latched (unacknowledged)
08.34 GGB fail to close latched
Mask: 8000h
EG3500XT-P1
EG3500XT-P2
08.35 GGB fail to open latched
Mask: 4000h
EG3500XT-P1
EG3500XT-P2
08.27 Missing easYgen
Mask: 2000h
All
08.28 Missing LS5
Mask: 1000h
EG3500XT-P1
EG3500XT-P2
05.18 Cylinder temperature level 1
Mask: 0800h
All
05.19 Cylinder temperature level 2
Mask: 0400h
All
05.20 Cylinder temperature wire break
Mask: 0200h
All
6.35 Pole slip
Mask: 0100h
All
08.44 Syst.update LS5
Mask: 0080h
EG3500XT-P1
EG3500XT-P2
08.43 Syst.update easYgen
Mask: 0040h
All
06.32 Gen.AC Wiring
Mask: 0020h
All
06.33 Busbar1 AC Wiring
Mask: 0010h
EG3500XT-P2
08.29 CANopen error interface 3
Mask: 0008h
EG3500XT-P1
EG3500XT-P2
Internal
Mask: 0004h
Internal
Mask: 0002h
Internal
Mask: 0001h
50118
uint16
4193
BITLIST Alarms 3 active
GGB fail to close
Mask: 8000h
EG3500XT-P1
EG3500XT-P2
GGB fail to open
Mask: 4000h
EG3500XT-P1
EG3500XT-P2
Missing easYgen
Mask: 2000h
All
Missing LS5
Mask: 1000h
EG3500XT-P1
EG3500XT-P2
Temperature deviation level 1
Mask: 0800h
All
Temperature deviation level 2
Mask: 0400h
All
Temperature deviation wire break
Mask: 0200h
All
1004
easYgen-3000XT Series
B37574
9 Appendix
9.2.7 Protocol 5016 (Basic Visualization)
Released