Fig. 112:
Mains decoupling screen 3
Fig. 113:
Mains decoupling screen 4
4.1.5.14 Test mains decoupling (VDE AR-N 4105)
Symbol/Softkey
Description
Starts a special TEST mode which allows mains decoupling test independent
from breaker status (even if not mains parallel; GCB open, no rotation of prime
mover/generator).
Stops the TEST mode so mains decoupling is possible if system is mains parallel
only.
Notes:
TEST mode is deactivated not only by this button but too:
• ... if firing speed is reached
•
or
• ... automatically after 60 minutes
•
*
Indicates parameters that are part of the mains decoupling configuration.
149
easYgen-3000XT Series
B37574
4 Configuration
4.1.5.14 Test mains decoupling (VDE AR-N 4105)
Released