Trigger pole slip alarm
If the number of pole slip events are equal or higher than the configurable limit.
Reset pole slip event counter
If, during released pole slip monitoring, no pole slip event is encountered anymore for a
configurable time, the event counter is reset.
ID
Parameter
CL
Setting range
[Default]
Description
2416
Monitoring
2
On
Enabling the pole slip monitoring.
On: Monitoring is enabled
[Off]
Off: Monitoring is disabled
2417
Minimum active
power
2
0 to 150%
With reaching once this minimum
active power in parallel operation
the pole slip monitoring is
released. The entry is related to
generator rated power.
[10%]
2418
Limit active power
difference
2
0 to 150%
This difference between real
power and set point triggers the
monitoring. If the difference is
higher than the configured
threshold the pole slip events are
taken into account.
[10%]
2426
Pole slip with current
limit
2
On
Use additional the generator
current limit for detecting pole slip
events.
On: Current limit is additional
used for pole slip detection
[Off]
Off: Current limit is not used
2427
Generator current
limit
2
50 to 200%
If the generator current is higher
than the threshold during active
power decreasing the current
condition for pole slip events is
matched.
[110%]
2428
Pole slip with pickup
2
On
Use additional the difference
between pickup and generator
frequency for detecting pole slip
events
On: Use the difference between
pickup and frequency
[Off]
Off: Difference between pickup
and frequency is not used
2429
Speed/frequency
difference
2
0.5 to 9.9 Hz
If the difference between speed
and frequency is higher than the
threshold the pickup condition for
pole slip events is matched. The
pickup speed is calculated to
frequency for the compare with
the generator frequency from the
AC measurement.
[2.0 Hz]
2419
Number of pole slip
events
2
1 to 10
This is the maximum allowed
number of pole slips to trigger the
alarm.
[2]
467
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.6.3 Pole Slip Monitoring
Released