ID
Parameter
CL
Setting range
[Default]
Description
This value refers to the Generator
rated voltage (parameter
).
3904
Delay
2
0.02 to 99.99 s
[5.00 s]
If the monitored generator voltage
asymmetry exceeds the threshold
value for the delay time
configured here, an alarm will be
issued.
Notes
If the monitored generator voltage
asymmetry falls below the
threshold (minus the hysteresis)
before the delay expires the time
will be reset
3901
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class F]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
3902
Self acknowledge
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
3905
Enabled
2
Always
Monitoring for this fault condition
is continuously enabled.
[87.70 LM:Eng.mon]
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
427
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.2.3 Generator Voltage Asymmetry
Released