Message text
ID
Meaning
The easYgen has attempted to open the GCB within the configured time and
failed.
GCB syn. timeout
3064
GCB synchronization time exceeded
The easYgen has failed to synchronize the GCB within the configured
synchronization time.
GCB failure 50BF
10668
GCB failure 50BF
Generator current is measured even if the mains repliy signals GCB open.
MCB fail to close
2623
MCB failed to close
The easYgen has attempted to close the MCB the configured maximum number of
attempts and failed. Depending on the configuration, the easYgen will continue to
attempt to close the GCB as long as the conditions for closing the MCB are
fulfilled.
MCB fail to open
2624
Failed MCB open
The easYgen is still receiving the reply MCB closed" after the MCB open monitoring
timer has expired.
MCB syn. timeout
3074
MCB synchronization time exceeded
The easYgen has failed to synchronize the MCB within the configured
synchronization time.
MCB failure 50BF
10670
MCB failure 50BF
There is a mains current measured even the MCB reply signals MCB open.
MCB plausibility
10672
MCB plausibility
The number of closed MCBs is different to the number of easYgen devices in the
same segment.
N-cont. reply mism.
5153
Neutral contactor reply mismatch
Neutral contactor reply mismatch to the NC command.
9.5.5.9
CANopen Monitoring
Message text
ID
Meaning
CANopen Interface 1
10087
Interface alarm CANopen on CAN bus 1
No Receive Process Data Object ( RPDO) is received within the configured time.
CANopen Interface 2
10088
Interface alarm CANopen on CAN bus 2
No message is received from the external expansion board (Node-ID) within the
configured time.
CANopen Interface 3
10090
Interface alarm CANopen on CAN bus 3
No Receive Process Data Object ( RPDO) is received within the configured time.
1187
easYgen-3000XT Series
B37574
9 Appendix
9.5.5.9 CANopen Monitoring
Released