NEW LogicsManager to disable all load ramps (BDEW)
With LogicsManager
It is possible to activate the fastest load ramp e.g., for
test.
4.4.4.5.1
Configure: Load Control (general)
ToolKit: find settings screen
Analog Managers to define input signal of load setpoint (1, 2, 3, 4) are available in ToolKit
by
• a click from screen/page "Configure voltage control"
•
◦ on the button "Analog manager" in the left sidebar (below permanent buttons)
◦
or
◦ on "next page", or
◦
• search for one of the load controlled value shown at the status screen
•
ToolKit: Trend chart
ToolKit offers a trend visualization accessible by
• a click from screen/page "General load control"
•
◦ on the button "Trend chart" in the left sidebar (below permanent buttons) or
◦
◦ on "next page", or
◦
ID
Parameter
CL
Setting range
[Default]
Description
5525
Load control
2
[PID analog]
The generator load is controlled
using an analog PID controller.
3pos controller
The generator load is controlled
using a three-step controller.
Off
Load control is not carried out.
5513
Proportional gain
2
0.01 to 100.00
[1.00]
The proportional coefficient
specifies the gain. By increasing
the gain, the response is
increased to permit larger
corrections to the variable to be
controlled.
The farther out of tolerance the
process is the larger the response
action is to return the process to
the tolerance band.
Notes
If the gain is configured too high,
the result is excessive overshoot/
undershoot of the desired value.
351
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.5.1 Configure: Load Control (general)
Released