oscillation may occur if the ramp
is configured too high.
11978
2nd load control
setpoint ramp
2
Determined by LogicsManager
87.77
[(0 & 02.02) & 02.02]
The LogicsManager can be used to
switch from load ramp 1 to load
ramp 2 settings.
If this LogicsManager condition is
TRUE and load ramp will be
performed, »Load control setpoint
ramp 2« will be used.
5015
Time until decoupl.
ramp reset
2
0 to 9999 s
[0 s]
The mains decoupling ramp (2nd
load ramp) will be disabled after
that time delay.
Notes
This parameter comes with
default zero for backward
compatibility (2nd load ramp
disabled). BDEW prefers 600 s.
5016
Load control setpoint
ramp 3
2
0.10 to 100.00%/s
[3.00%/s]
The different setpoint values are
supplied to the controller via this
ramp. The slope of the ramp is
used to alter the rate at which the
controller modifies the setpoint
value. The faster the change in
the setpoint is to be carried out,
the greater the value entered here
must be.
Notes
This ramp is also used in islanded
operation for loading or unloading
an additional genset. An excessive
oscillation may occur if the ramp
is configured too high.
11998
3rd load control
setpoint ramp
2
Determined by LogicsManger
87.79
[(02.02 & 02.02) & 02.02]
The LogicsManager can be used to
switch from load ramp 1 or load
ramp 2 to load ramp 3 settings. If
this LogicsManager condition is
TRUE and load ramp will be
performed, [Load control setpoint
ramp 3] will be used. (3rd load
control setpoint ramp has the
highest priority.)
12853
Disable load setpoint
ramp
2
Determined by LogicsManager
87.76
[(02.01& 1) & 1]
The LogicsManager can be used to
perform fastest possible load
ramp independent from load ramp
settings.
If this LogicsManager condition is
TRUE and load ramp will be
performed, e.g. a test with
different setpoint steps but
without any ramping is possible
like requested by BDEW.
5569
Load control
unloading ramp
2
0.10 to 100.00%/sec
[3.00%/sec]
The ramp rate is used for the
unloading in parallel operation or
islanded operation.
355
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.5.1 Configure: Load Control (general)