ID
Parameter
Setting range
[Default]
Description
5831
P/Pinst. point 1
0
Configuration points (reference
points 1 to 10 with relation active
power/active power installed (P/
Pinst) and rated reactive power in
relation to active power installed
(Q/Pinst)
P:
Range 0.00 .. 1.50
Format 0.00
5832
Q/Pinst. point 1
0
5833
P/Pinst. point 2
0.1
5834
Q/Pinst. point 2
0
5835
P/Pinst. point 3
0.2
5836
Q/Pinst. point 3
0
5837
P/Pinst. point 4
0.3
5838
Q/Pinst. point 4
0
5839
P/Pinst. point 5
0
5840
Q/Pinst. point 5
0
5841
P/Pinst. point 6
0.5
5842
Q/Pinst. point 6
0
5843
P/Pinst. point 7
0.6
5844
Q/Pinst. point 7
0.05
5845
P/Pinst. point 8
0.9
5846
Q/Pinst. point 8
0.33
5847
P/Pinst. point 9
1
5848
Q/Pinst. point 9
0.33
5849
P/Pinst. point 10
1.5
5850
Q/Pinst. point 10
0.33
1898
Q(P) setpoint filter
0 to 99.9s
[10.0 s]
The PT1-filter for the reactive
power characteristic Q(P) can be
configured here. The parameter
stands for the 3 times tau value of
a PT1 element. (see drawing).
That means the configured time
defines when 95% of the original
setpoint jump is reached.
Note: Input 0.0s disables the filter
influence.
Visualization Q(P) reactive power characteristic
Actual value P/Pinst ID10354
Q/Pinst reference ID10349
QP reference [kvar] ID10350
324
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.5.2 Reactive Power Q(P)
Released