ID
Parameter
CL
Setting range
[Default]
Description
[Off]
Monitoring is disabled.
3154
Delay
2
0.01 to 650.00 s
[0.20 s]
The maximum receiving break is
configured with this parameter.
If the interface does not receive
an RPDO within this time, the
action specified by the alarm class
is initiated. The delay timer is re-
initialized after every message is
received.
3151
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
3152
Self acknowledge
2
[Yes]
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
3153
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
559
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.4 CAN Interface 1
Released