Free Alarm 1 for example
ID
Parameter
CL
Setting range
[Default]
Description
8120
Free alarm 1
2
Determined by LogicsManager
88.01
[02.01 LM FALSE & 1 & 1]
= 11550
This LogicsManager is used to
select the source of monitoring.
Notes
For information on the
LogicsManager and its default
settings see
.
8121
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
The assigned independent alarm
class specifies what action should
be taken when the alarm becomes
TRUE.
[Class B]
8122
Self acknowledge
2
Yes / No
The control automatically clears
the alarm if the fault condition is
no longer detected.
[No]
The control does not automatically
clears the alarm if the fault
condition is no longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
8123
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
8236
Delay
2
0.02 to 99999.99 s
Period before alarm becomes
TRUE.
[1.00 s]
6680
Description
2
[Free alarm 1]
...((30 characters))*
Text is configurable by ToolKit.
Notes
*) The max. number of characters
is 48 but 30 characters can be
read on easYgen HMI without
restrictions.
557
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.2 Free Configurable Alarms
Released