ID
Parameter
Setting range
[Default]
Description
5829
Mains test voltage
50 to 150%
[100%]
The Q(V) function uses the mains
test voltage for the calculation of
the reactive power reference.
Note: Only in toolkit!
4.4.4.2.5.2 Reactive Power Q(P)
General notes
The FNN VDE-AR-N 4105 / 4110 requests different methods for reactive power control
during mains faults to stabilize the mains. This method determines a reactive power
based on the actual power output of the generator. The reactive power is controlled in
relation to the actual active power. Maximal 10 reference points define the curve. The
space between the points are linear interpolated. The tolerance band for the configured
curve is +/- 2%
Function
Through the input of up to 10 points a reactive power characteristic can be formed.