Furthermore the function provides the capability to shift point 1 on the x-axis from
outside. Through this it can be determined afterwards at what mains voltage level the
reactive power flow begins to work.
Through a dead band incorporation into the function the operator can determine to stay
on a last calculated reactive power. So as long the mains voltage deviates not again
around a dead band width the last setpoint is kept.
And finally through a test function the function gives the operator the opportunity to
simulate different mains voltages to observe whether the reactive power flow is
maintained properly.
Fig. 166:
EGXT_Example_of_a_Q(V)_characteristic
319
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.5.1 Reactive power Q(V)
Released