ID
Parameter
CL
Setting range
[Default]
Description
can be received via CAN 1 or
Ethernet.
Notes
The following alarms can be
triggered:
• Missing member 4105
•
• Para. alignment 4105
•
• Meas.difference 4105
•
3298
Monitoring mode
2
Single
The diagnostic function is related
to one partner unit.
[Multi]
The diagnostic function is
executed with according partner
units.
3299
Device number
partner
2
[01]
01 to 64
The device ID of the expected
partner unit. This configuration is
only valid, if the mode 'single' is
enabled.
1828
Voltage difference
2
[4.0%]
2.0 to 9.9%
This is the voltage measurement
tolerance for all participating 4105
partners relating to the mains
rated voltage measurement (refer
to ID
). This is a part
within the 4105 diagnostic.
1836
Frequency difference
2
[1.0%]
0.5 to 9.9%
This is the frequency
measurement tolerance for all
participating 4105 partners
relating to the system rated
frequency measurement. (refer to
ID
). This is a part within
the 4105 diagnostic.
Monitoring Missing Member AR-–4105
ID
Parameter
CL
Setting range
[Default]
Description
5125
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class C]
The alarm class specifies what
action should be taken in case of
missing communication with
devices(s) being member(s) of the
AR-–4105 system.
Notes
For additional information refer to
.
5126
Self acknowledge
2
Yes
The control automatically clears
the alarm if the fault condition is
no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
496
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.4.1 Setup Grid Code AR-–4105
Released