Parameter
Ext. AO 1
Ext. AO 2
Ext. AO 3
Ext. AO 4
Source value at
minimum level
10240
10250
10260
10270
Source value at
maximum level
10241
10251
10261
10271
Filter time
constant
10239
10249
10259
10269
Selected hardware
type
10238
10248
10258
10268
Setting range: Off; mA; V
Minimum hardware
level
10242
10252
10262
10272
Maximum
hardware level
10243
10253
10263
10273
Ext. analog output
{x}
(displayed in
ToolKit only: ON/
OFF)
10245
10255
10265
10275
Notes:
Refer to
for details and definition of the parameters.
Table 50: External analog outputs {1 to 4} - parameter IDs
ID
Parameter
CL
Setting range
[Default]
Description
10237
10247
10257
10267
AM Data source
ext.AO1
2
Determined by AnalogManager
93.21 .. 93.24
AO1 to AO 4: [A1 = "11.03
Speed bias [%]"]
The data source may be selected
from the available data sources.
Notes
for a list of all data sources.
10238
10248
10258
10268
Selected hardware
type
2
This parameter is used to
configure the appropriate type of
analog controller signal. The range
of the analog output is configured
here.
[Off]
No analog output signal will be
issued.
mA
V
10242
20252
10262
10272
Minimum hardware
level
(User defined minimum
output value)
2
0.00 to 20.00
[0.00]
The value of the configured
hardware range, which shall
correspond with the configured
minimum source value, must be
entered here (y-axis). This
specifies the minimum limit of the
hardware range.
Example
If the value configured here is 2.5,
the maximum output range of
259
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.7 External Analog Outputs