ID
Parameter
CL
Setting range
[Default]
Description
Off
Monitoring is disabled for Level 1
limit and/or Level 2 limit.
2354
2360
Limit
2
50.0 to 300.0%
2354: [105.0%]
2360: [110.0%]
(Hysteresis: 1%)
(Reset Delay: 80 ms)
The percentage values that are to
be monitored for each threshold
limit are defined here.
If this value is reached or
exceeded for at least the delay
time without interruption, the
action specified by the alarm class
is initiated.
Notes
This value refers to the Generator
rated active power
(parameter
2355
2361
Delay
2
0.02 to 99.99 s
2355: [5.00 s]
2361: [0.10 s]
If the monitored generator load
exceeds the threshold value for
the delay time configured here, an
alarm will be issued.
Notes
If the monitored generator load
falls below the threshold (minus
the hysteresis) before the delay
expires the time will be reset.
2351
2357
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
2351: [Class B]
2357: [D]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
2352
2358
Self acknowledge
4
Yes
The control automatically clears
the alarm if the fault condition is
no longer detected.
[No]
The control does not automatically
reset the alarm when the fault
condition is no longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2353
2359
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
443
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.5.2 Generator Overload MOP (Level 1 & 2) ANSI# 32
Released