4.4.5
Configure Operation Modes
4.4.5.1
Operation Modes: General
Priority of operation modes
The priority of operation modes is well defined from highest to lowest priority:
• »STOP« is higher than
•
• »AUTOMATIC« is higher than
•
• »MANUAL« is higher than
•
• »TEST«
•
ID
Parameter
CL
Setting range
[Default]
Description
1795
Startup in mode
(Operating mode after
applying the power
supply )
2
If the controller is powered down,
the unit will start in the following
configured mode when it is
powered up again.
[STOP]
The unit starts in the STOP
operating mode.
AUTO
The unit starts in the AUTOMATIC
operating mode.
MAN
The unit starts in the MANUAL
operating mode.
LLast
The unit starts in the last
operating mode the control was in
prior to being de-energized.
TEST
The unit starts in the TEST
operating mode.
Notes
For the selection of the operating
mode via the LogicsManager (if
two different operating modes
have been selected
simultaneously) the control unit
will prioritize the modes as
follows:
• 1. STOP
•
• 2. AUTOMATIC
•
• 3. MANUAL
•
• 4. TEST
•
12510
Operat. mode AUTO
(Activate operating
mode AUTOMATIC )
2
WARNING!
In Operation mode AUTO
(intentionally):
• the STOP button on front
•
panel is without function and
• the soft buttons for operation
•
mode selection are not
displayed.
Notes
380
easYgen-3000XT Series