Example: Hardware range 4 to 20 mA mapped to 0 to 1000 display value
4
0
10
0
display
min. = 4
1000
20
display
max.
= 20
Sender value at
Sender value
at
Sender value at
Sender value at
Example:
How the hardware level
4 – 20 mA of the analog input
maps the display values 0 - 1000
y: Display value
(e.g. [kW])
x: Sender value
(e.g. [mA])
display value = 1000
display value = 0
Fig. 156:
Analog Input Mapping
ID
Parameter
CL
Setting range
[Default]
Description
1020
1070
1120
Sender type
2
The software in the control unit
may be configured for various
types of sensors. The configurable
ranges apply to the linear analog
input.
[0 - 2000 Ohm]
The measuring range of the
analog input is 0 to 2000 Ohms.
0 - 20mA
The measuring range of the
analog input is 0/4 to 20 mA.
0-1V
The measuring range of the
analog input is 0 to 1 V.
Notes
If parameter "Type" (
"VDO xx" or "Pt100", this
parameter must be configured to
"0 to 2000 Ohm"!
1046
1096
Offset
2
-20.0 to 20.0 Ohms
[0.0 Ohm]
The resistive input (the "0 to 2000
Ohms" analog input) may be
calculated with a permanent
offset to adjust for inaccuracies.
246
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.4.2 Analog Inputs 1 to 3 (0 to 2000 Ω | 0/4 to 20 m A | 0 to 1 V)
Released