ID
Parameter
CL
Setting range
[Default]
Description
15026
LDSS with predicted
load
2
Determined by LogicsManager
86.36
[(0 & 1) & 1]
If the conditions of this
LogicsManager have been fulfilled
LDSS is working with predicted
load. Otherwise LDSS is working
normally.
9066
Predicted load source
2
Internal
[External]
Internal: LDSS with predicted load
is using internal data. ("86.09 LM:
Start req.in AUTO") and "81.30 AM
Consumer load [kW]")
External: LDSS with predicted load
is expected data from external via
RPDOs
9059
AM Consumer load
[kW]
2
AnalogManager
]
The result (81.30) of this analog
manager provides the load for the
load prediction in internal source
mode
4.4.6
Emergency Run
General notes
The emergency power operation is possible only in application mode
A04
(2 power circuit
breakers).
If the LogicsManager outputs 'Stop request in AUTO' or 'Inhibit emergency run' are TRUE,
an emergency power operation may be prevented or interrupted from an external
source.
Prerequisites
• The emergency power function can only be activated for synchronous generators
•
• Emergency power is carried out in operating mode AUTOMATIC regardless of the
•
status of the LogicsManager output 'Start request in AUTO' (LogicsManager).
The display indicates "Emergency run" during emergency power operation.
The following principles are observed in case of an emergency power operation:
• If an emergency power operation is initiated, the engine is started automatically,
•
unless the start sequence is interrupted via an alarm or prevented via the
LogicsManager or the operating mode is changed.
• The GCB can be closed regardless of the engine delay time if the generator
•
frequency and voltage are within the configured operating limits (
Generator Operating Ranges: Voltage / Frequency / Busbar”
) if the parameter
"Undelay close GCB" (parameter
) has been set accordingly (default
setting).
417
easYgen-3000XT Series
B37574
4 Configuration
4.4.6 Emergency Run