SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
321
2 Parameters
2.2 List of parameters
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
Refer to: F01910
Description:
Connector input for the sign-of-life of the clock synchronous PROFIBUS/PROFINET controller.
The sign-of-life is expected at bits 12 to 15. Bits 0 to 11 are not evaluated.
The sign-of-life signal is normally received in PZD4 (control word 2) from the controller.
Dependency:
Refer to: p0925, r2065
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
For controller STOP, the additional monitoring time is not effective.
Description:
Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
p2044
PROFIdrive fault delay / PD fault delay
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
0 [s]
100 [s]
0 [s]
p2045
CI: PB/PN clock synchronous controller sign-of-life signal source /
PB/PN ctrSoL s_src
Access level:
3
Calculated:
-
Data type:
U32 / Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
- - 0
p2047
PROFIBUS additional monitoring time / PB suppl t_monit
CU250S_V_DP
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
0 [ms]
20000 [ms]
0 [ms]
r2050[0...11]
CO: PROFIBUS PZD receive word / PZD recv word
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2440, 2468, 9360
Min Max
Factory