2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
374
List Manual, 09/2017, A5E33842890
Description:
Sets the time constant for the setpoint filter (PT1) of the technology controller.
Description:
Display and connector output for the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
Description:
Sets the type of technology controller.
Value:
0:
D component in the actual value signal
1:
D component in system deviation
Description:
Sets the signal source for the actual value of the technology controller.
Description:
Sets the time constant for the actual value filter (PT1) of the technology controller.
p2261
Technology controller setpoint filter time constant / Tec_ctrl set T
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]
r2262
CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7958
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2263
Technology controller type / Tec_ctrl type
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0 1 0
p2264[0...n]
CI: Technology controller actual value / Tec_ctrl act val
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 0
p2265
Technology controller actual value filter time constant / Tec_ctrl act T
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]