2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
206
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enable ramp-function generator.
Dependency:
Refer to: r0054, p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enable ramp-function generator.
Dependency:
Refer to: r0054, p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / Enable RFG
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501
Min Max
Factory
setting
- - [0]
2090.4
[1] 1
[2] 2090.4
[3] 2090.4
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / Enable RFG
CU250S_V
CU250S_V_CAN
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501
Min Max
Factory
setting
- - 1
p1141[0...n]
BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501
Min Max
Factory
setting
- - [0]
2090.5
[1] 1
[2] 2090.5
[3] 2090.5