SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
189
2 Parameters
2.2 List of parameters
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has been
switched off.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the setpoint
must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
Description:
Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
p1039[0...n]
BI: Motorized potentiometer inversion / MotP inv
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
- - 0
p1040[0...n]
Motorized potentiometer starting value / Mop start value
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3020
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1041[0...n]
BI: Motorized potentiometer manual/automatic / Mop manual/auto
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
- - 0
p1042[0...n]
CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
- - 0
p1043[0...n]
BI: Motorized potentiometer accept setting value / MotP acc set val
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
- - 0