SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
51
2 Parameters
2.2 List of parameters
Description:
Sets the number of Drive Data Sets (DDS).
Dependency:
Refer to: p0010, r3996
Notice:
When the data sets are created, short-term communication interruptions may occur.
Description:
Assign a drive data set (= index) the corresponding encoder data set (EDS) for encoder 1.
The value corresponds to the number of the assigned encoder data set.
Example:
Encoder 1 in drive data set 2 should be assigned encoder data set 0.
--> p0187[2] = 0
Note:
A value of 99 means that no encoder has been assigned to this drive data set (not configured).
Description:
Assign a drive data set (= index) the corresponding encoder data set (EDS) for encoder 2.
The value corresponds to the number of the assigned encoder data set.
Example:
Encoder 2 in drive data set 2 should be assigned to encoder data set 1.
--> p0188[2] = 1
Note:
A value of 99 means that no encoder has been assigned to this drive data set (not configured).
Description:
Displays the bootloader version.
Index 0:
Displays the bootloader version.
Index 1:
Displays the bootloader version 3 (for CU320-2 and CU310-2)
Value 0 means that boot loader 3 is not available.
Dependency:
Refer to: r0018, r0148, r0198
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
p0180
Number of Drive Data Sets (DDS) / DDS count
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(15)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8565
Min Max
Factory
setting
1 4 1
p0187[0...n]
Encoder 1 encoder data set number / Enc 1 EDS number
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(4)
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8570
Min Max
Factory
setting
0 99
0
p0188[0...n]
Encoder 2 encoder data set number / Enc 2 EDS number
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(4)
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8570
Min Max
Factory
setting
0 99
1
r0197[0...1]
Bootloader version / Bootloader vers
Access level:
4
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -