2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
608
List Manual, 09/2017, A5E33842890
Description:
Sets the test stop mode for the safety digital output (F-DO)
Value:
1:
Test mode 1 evaluation of int. diagnostic signal (passive load)
2:
Test mode 2 read back F-DO in DI (relay circuit)
3:
Test mode 3 read back F-DO in DI (actuator with feedback signal)
Dependency:
Refer to: p10001, p10003, p10007, p10046
Description:
Displays the monitoring status of the fail-safe digital inputs (F-DI).
The F-DIs that are being used by the Safety Integrated functions are displayed.
If the module used has fewer than 3 F-DIs, "Freely available" is displayed for the F-DIs which are not in use.
Dependency:
p10006 / p10106
p10022 / p10122
p10023 / p10123
p10026 / p10126
p10030 / p10130
p10031 / p10131
p10050 / p10150
Refer to: r10049
Description:
Setting for the transfer and evaluation of fail-safe digital inputs (F-DI) via PROFIsafe.
The safe state of the selected F-DIs is transferred to the F-control via PROFIsafe. The F-DIs are monitored for
discrepancies. Discrepancy faults can be acknowledged via PROFIsafe.
Dependency:
Refer to: p10050
Note:
F-DI: Fail-safe Digital Input
p10147
SI Motion F-DO test stop mode (processor 2) / SI F-DO testmodeP2
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
1 3 2
r10149
SI Motion F-DI monitoring status (processor 2) / SI F-DI status P2
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
F-DI 0
Safety monitored
Freely available
-
01
F-DI 1
Safety monitored
Freely available
-
02
F-DI 2
Safety monitored
Freely available
-
p10150
SI Motion PROFIsafe F-DI transfer (processor 2) / SI Ps F-DI tran P2
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
F-DI 0 processor 2
Transfer
No transfer
-
01
F-DI 1 processor 2
Transfer
No transfer
-
02
F-DI 2 processor 2
Transfer
No transfer
-