SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
113
2 Parameters
2.2 List of parameters
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Reserved
Dependency:
Refer to: p0496, r0497, r0499
Description:
Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Reserved
Dependency:
Refer to: p0496, r0497, r0498
Description:
Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0340 = 5.
Value:
0:
Standard drive
1:
Pumps and fans
2:
Sensorless closed-loop control down to f = 0 (passive loads)
3:
Pumps and fans, efficiency optimization
5:
Starting with a high break loose torque
Dependency:
For p0096 = 1, 2 (Standard, Dynamic Drive Control) p0500 cannot be changed.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Notice:
If the technological application is set to p0500 = 0 ... 3 during commissioning (p0010 = 1, 5, 30), the operating mode
(p1300) is pre-set accordingly.
Note:
The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
For p0500 = 0 and when the calculation is initiated, the following parameters are set:
- p1574 = 10 V
- p1750.2 = 0
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0, PM260: p1802 = 2)
- p1803 = 106 % (PM260: p1803 = 103 %)
- p3855
For p0500 = 1 and when the calculation is initiated, the following parameters are set:
- p1574 = 2 V
- p1750.2 = 0
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0)
- p1803 = 106 % (PM260: p1803 = 103 %)
For p0500 = 2 and when the calculation is initiated, the following parameters are set:
- p1574 = 2 V (separately excited synchronous motor: 4 V)
- p1750.2 = 1
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0)
- p1803 = 106 % (PM260: p1803 = 103 %)
r0499[0...2]
CO: Encoder diagnostic signal high word / Enc diag high word
Access level:
4
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p0500
Technology application / Tec application
PM240
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1, 5), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 5 0