SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
417
2 Parameters
2.2 List of parameters
Dependency:
Refer to: p2609
Description:
Sets the approach velocity after detecting the zero mark to approach the reference point.
Dependency:
Refer to: p2595, p2597, p2604, p2607, p2609, p2610
Note:
When traversing to the reference point, the velocity override is not effective.
Description:
Sets the signal source for the reference cam.
Dependency:
Refer to: p2607
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the reversing cam in the negative direction of travel.
1 signal: Reversing cam not reached.
0 signal: Reversing cam reached.
Dependency:
Refer to: p2614
Note:
If, during the search for reference from the reversing cam minus and plus, a 0 signal is detected, then the axis
remains stationary (at standstill).
Description:
Sets the signal source for the reversing cam in the negative direction of travel.
1 signal: Reversing cam not reached.
0 signal: Reversing cam reached.
Dependency:
Refer to: p2613
Note:
If, during the search for reference from the reversing cam minus and plus, a 0 signal is detected, then the axis
remains stationary (at standstill).
p2611
EPOS search for reference approach velocity reference point / v_appr ref_pt
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3612
Min Max
Factory
setting
1 [1000 LU/min]
40000000 [1000 LU/min]
300 [1000 LU/min]
p2612
BI: EPOS search for reference reference cam / Ref_cam
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3612
Min Max
Factory
setting
- - 0
p2613
BI: EPOS search for reference reversing cam minus / Rev minus
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3612
Min Max
Factory
setting
- - 1
p2614
BI: EPOS search for reference reversing cam plus / Rev plus
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3612
Min Max
Factory
setting
- - 1