2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
506
List Manual, 09/2017, A5E33842890
Description:
Sets the time [ms] to cyclically send heartbeat telegrams.
The smallest cycle is 100 ms.
For p8606 = 0, heartbeat telegrams are not sent.
Dependency:
Refer to: p8604
Note:
Corresponds to the CANopen object 1017 hex.
Activating the heartbeat protocol automatically deactivates the node guarding.
Description:
General device information display.
Index:
[0] = Vendor ID
[1] = Product code
[2] = Revision number
[3] = Serial number
Note:
Corresponds to the CANopen object 1018 hex.
For index 3:
The SINAMICS serial number comprises 60 bits.
Of these bits, the following are displayed in this index:
Bits 0 ... 19: Consecutive number
Bit 20 ... 23: reserved
Bits 24 ... 27: Month of manufacture (0 means January, B means December)
Bits 28 ... 31: Year of manufacture (0 means 2002)
Description:
As a result of a Bus Off error, the CAN controller is set into the initialization state.
Index 0:
The CAN controller is manually started after resolving the cause of the error with p8608[0] = 1.
Index 1:
The automatic CAN bus start function is activated using p8608[1] = 1.
At 2 second intervals, the CAN controller is automatically restarted until the cause of the error has been resolved and
a CAN connection has been established.
Value:
0:
Inactive
1:
Start CAN controller
Index:
[0] = Manual controller start function
[1] = Activating the automatic controller start function
Note:
For index 0:
This parameter is automatically reset to 0 after start.
p8606
CAN Producer Heartbeat Time / Prod Heartb Time
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [ms]
65535 [ms]
0 [ms]
r8607[0...3]
CAN Identity Object / Identity object
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p8608[0...1]
CAN Clear Bus Off Error / Clear bus off err
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0