2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
378
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source to hold the integrator for the technology controller.
Description:
Sets the signal source for the precontrol signal of the technology controller.
Description:
Sets the signal source to enable the technology controller output.
The technology controller output is enabled with a 1 signal.
The technology controller output is held with a 0 signal.
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
p2286[0...n]
BI: Hold technology controller integrator / Tec_ctr integ hold
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 56.13
p2289[0...n]
CI: Technology controller precontrol signal / Tec_ctr prectr_sig
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 0
p2290[0...n]
BI: Technology controller limiting enable / Tec_ctrl lim enab
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 1
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_lim
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]