SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
487
2 Parameters
2.2 List of parameters
Dependency:
Refer to: p5391
Refer to: F07011, A07012, A07014
Note:
For firmware version < 4.7 SP6: parameter p5391 is not visible for users (this is a Siemens internal parameter).
Description:
Displays the PROFIenergy mode ID of the effective energy-saving mode.
Value:
0:
POWER OFF
2:
Energy-saving mode 2
240:
Operation
255:
Ready
Note:
Pe: PROFIenergy profiles
Description:
Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, time of minimum stay
Index:
[0] = Reserved
[1] = Mode 2
Note:
It is not permissible that the value is less than the sum of the "energy-saving mode transition time" and the "operating
state transition time" (system properties).
Pe: PROFIenergy profiles
Description:
Sets the time of maximum stay for the energy-saving mode.
Index:
[0] = Reserved
[1] = Mode 2
Note:
Pe: PROFIenergy profiles
r5600
Pe energy-saving mode ID / Pe mode ID
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2381, 2382
Min Max
Factory
setting
0 255
-
p5602[0...1]
Pe energy-saving mode pause time minimal / Pe mod t_pause min
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2381
Min Max
Factory
setting
300000 [ms]
4294967295 [ms]
[0] 300000 [ms]
[1] 480000 [ms]
p5606[0...1]
Pe energy-saving mode time of maximum stay / Pe t_max_stay
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2381
Min Max
Factory
setting
0 [ms]
4294967295 [ms]
4294967295 [ms]