SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
411
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for jog 2.
Dependency:
When jogging, the axis is accelerated or braked with the maximum acceleration/deceleration (p2572/p2573).
BI: p2591 = 0 signal
The axis endlessly moves with the setpoint velocity, jog 2 (p2586).
BI: p2591 = 1 signal
The axis traverses through a parameterized distance (p2586) with the setpoint velocity, jog 2 (p2588).
Refer to: p2572, p2573, p2586, p2588, p2591
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for jogging incremental.
Dependency:
Refer to: p2585, p2586, p2587, p2588, p2589, p2590
Description:
Sets the signal source for the reference of the internal length units LU to motor revolution for rotary encoders and to
mm for linear encoders.
Dependency:
Refer to: p0404, r2524, p2594
Note:
The signal value is used to convert the length unit to the speed or velocity setpoint.
Description:
Sets the signal source for the externally limited maximum velocity.
Index:
[0] = Setpoint limit absolute
[1] = Setpoint limiting positive
[2] = Setpoint limiting negative
Dependency:
Refer to: r2524, p2571, p2593
Warning:
In order that the externally limited velocity can be effective for the EPOS operating modes, connector input p2593
must be correctly interconnected.
p2590
BI: EPOS jog 2 signal source / Jog 2 S_src
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3610, 3625
Min Max
Factory
setting
- - 722.4
p2591
BI: EPOS jogging incremental / Jog incr
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3610
Min Max
Factory
setting
- - 722.5
p2593
CI: EPOS LU/revolution LU/mm / LU/rev LU/mm
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3630
Min Max
Factory
setting
- - 2524[0]
p2594[0...2]
CI: EPOS Maximum velocity externally limited / v_Max ext lim
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3630
Min Max
Factory
setting
- - 0