SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
337
2 Parameters
2.2 List of parameters
Description:
Setting to invert the individual binector outputs of the connector-binector converter.
Using p2098[0], the signals of connector input p2099[0] are influenced.
Using p2098[1], the signals of connector input p2099[1] are influenced.
Dependency:
Refer to: r2094, r2095, p2099
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
Refer to: r2094, r2095
Note:
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2098[0...1]
Inverter connector-binector converter binector output / Con/bin outp inv
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2468, 9360
Min Max
Factory
setting
-
-
0000 0000 0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Bit 0
Inverted
Not inverted
-
01
Bit 1
Inverted
Not inverted
-
02
Bit 2
Inverted
Not inverted
-
03
Bit 3
Inverted
Not inverted
-
04
Bit 4
Inverted
Not inverted
-
05
Bit 5
Inverted
Not inverted
-
06
Bit 6
Inverted
Not inverted
-
07
Bit 7
Inverted
Not inverted
-
08
Bit 8
Inverted
Not inverted
-
09
Bit 9
Inverted
Not inverted
-
10
Bit 10
Inverted
Not inverted
-
11
Bit 11
Inverted
Not inverted
-
12
Bit 12
Inverted
Not inverted
-
13
Bit 13
Inverted
Not inverted
-
14
Bit 14
Inverted
Not inverted
-
15
Bit 15
Inverted
Not inverted
-
p2099[0...1]
CI: Connector-binector converter signal source / Con/bin S_src
Access level:
3
Calculated:
-
Data type:
U32 / Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2468, 9360
Min Max
Factory
setting
- - 0
p2100[0...19]
Change fault response fault number / Chng resp F_no
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8050, 8075
Min Max
Factory
setting
0 65535
0