SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
165
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master control by PLC.
p0852[0...n]
BI: Enable operation/inhibit operation / Enable operation
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501, 8820, 8920
Min Max
Factory
setting
- - [0]
2090.3
[1] 1
[2] 2090.3
[3] 2090.3
p0852[0...n]
BI: Enable operation/inhibit operation / Enable operation
CU250S_V
CU250S_V_CAN
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501, 8820, 8920
Min Max
Factory
setting
- - 1
p0854[0...n]
BI: Control by PLC/no control by PLC / Master ctrl by PLC
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501, 8720, 8820,
8920
Min Max
Factory
setting
- - [0]
2090.10
[1] 1
[2] 2090.10
[3] 2090.10