2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
528
List Manual, 09/2017, A5E33842890
Note:
The following BICO interconnections are automatically established if the CANopen control word is mapped at one of
the locations x = 0 ... 3 in the receive process data buffer.
BI: p0840.0 = r209x.0
BI: p0844.0 = r209x.1
BI: p0848.0 = r209x.2
BI: p0852.0 = r209x.3
BI: p2103.0 = r209x.7
The write access is rejected if a CANopen control word is not mapped at one of these locations.
This also causes the project download of the commissioning software to be canceled.
Description:
Setting for the CANopen control word bit 8 "Stop" (CANopen STW.8).
Value:
-1:
No interconnection
1:
Interconnection CANopen STW.8 with p1142
3:
Interconnection CANopen STW.8 with p1140
Dependency:
Refer to: r2050, r8750, r8795
Note:
Corresponds to CANopen object 605D hex.
The BICO interconnection is established, if the CANopen control word is mapped at one of the locations x = 0 ... 3 in
the receive process data buffer.
Description:
Display and connector output to interconnect standardized I16 setpoint CANopen objects of the velocity mode for
SDO transfer.
An index can only be used, if the corresponding object has not been mapped in a PDO.
Index:
[0] = VL Target Velocity
Note:
For index 0:
Corresponds to the CANopen object 6042 hex.
The displayed parameter value is scaled via the reference speed p2000:
4000 hex corresponds to p2000
Description:
Access to the CANopen control word using SDO transfer.
p8791
CAN stop option code / Stop opt_code
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-1 3 -1
r8792[0]
CO: CAN velocity mode I16 setpoint / Vel mod I16 set
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r8795.0...15
CO/BO: CAN control word / Control word
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
Do not activate coast down
Yes
No
-
02
Do not activate a Quick Stop
Yes
No
-
03
Enable operation
Yes
No
-
04
Enable ramp-function generator
Yes
No
-
05
Continue ramp-function generator
Yes
No (freeze)
-
06
Enable speed setpoint
Yes
No
-
07
Acknowledge fault
Yes
No
-